Low subcool low superheat - Next in the series based on HVAC Refrigerant Diagnostic Quick Sheet Bryan talks Symptoms of Low Evaporator Airflow.Videos on Airflow from our friends at Tru ...

 
However, this time you consider the three main causes of low suction pressure and check superheat and subcooling to make the correct diagnosis. CAUSE #1: Insufficient heat getting to the evaporator. This can be caused by low airflow (e.g., dirty filter, slipping belt, undersized or restricted ductwork, dust and dirt buildup on blower wheel) or .... How to apply for intermittent leave walmart

Low airflow can be caused by a dirty or clogged air filter or a malfunctioning fan or blower motor, so be sure to investigate those components as the source of insufficient airflow. Low refrigerant charge. As seen in the table in Figure 2, a low refrigerant charge will result in a higher superheat and a lower subcooling and lower evaporator ...LOW SUPERHEAT LOW SUBCOOLING TXV. Low superheat indicates that there is an excess amount of refrigerant in the evaporator, or the heat load is not sufficient to vaporize the liquid refrigerant to vapor before it moves to the compressor resulting in compressor damage. Plugging of the evaporator coils can also result in low superheat.4. When ambient air temp (Outside air temp) is 75-85 degrees the superheat should be 12-15 degrees, if the ambient temperature is 85 degrees or over the superheat should be 8-12 degrees. 5. If superheat is low then flooding the evaporator. Note: Do not adjust charge yet. 6. If superheat is high then starving the evaporator. Note: Do not adjust ...Here are some other stats they provided: Static pressure = .46 Suction pressure= 134.7 Liquid pressure = 239 Superheat = 2.4 Subcooling = 3.5 Return temp = 72 Supply temp = 54. Seeing no reaction when manipulating the bulb is a concern. A 3 degree subcool is usually not indicative of a failed txv, could just be low on charge.This will cause the compressor superheat to be high. The 100 percent saturated vapor point in the evaporator will climb up the evaporator coil causing high superheats. ... However, the undercharged system will have low condenser subcooling levels. Service technicians often confuse an undercharged system with a restricted metering device.In this HVAC Training Video, I Explain Why we need to Measure the Refrigerant Charge with Subcooling when a TXV Metering Device is used. I Explain why the To...Suction pressure: 120psi (40F); Measured line temp: 57 => superheat: 17F. Delta T supply/return as measured indoors: 19F The system trips when first turning on. I monitored the pressures during startup and I get a spike in the discharge to ~375psi, and a drop in the suction, but I didn't see how low the pressure drops on the suction line.What is the superheat requirement of R-404A/507 hermetic compressors and condensing units? In order to assure that liquid refrigerant does not return to the compressor during the running cycle, attention must be given to maintaining proper superheat at the compressor suction inlet. Emerson recommends a minimum of 20F …When calculating superheat, we use the "dew point." We use the "bubble point when calculating subcooling. The saturation temperature is the range of temperatures between those two points; a temperature could be "interpreted" as negative superheat or subcooling when it is actually just in the saturated range. In air conditioning, the ...When the subcool is set at 8C, the cooling capacity of DME is 6.5% lower than R134a but the COP is 2.6% higher. Another important finding in this study is that the best performance of DME over R134a is obtained at low subcool and low superheat.Causes of Low Subcooling. Insufficient Refrigerant Charge. Leaks in the system. Refrigerant leaks are a common cause of low subcooling. When there’s not enough …SUPERHEAT/SUBCOOL CALCULATOR with Thermometer and P/T Chart (69196) OPERATING STEPS. 1. Press the power button. For SuperHeat or Low Side PT Data. Suction Line "Super Heat" Match low side manifold gauge reading (suction pressure) 2. Use the and to display the desired refrigerant. 3. Press ENTER. For SubCool or High Side PT Data. Liquid Line 4.Study with Quizlet and memorize flashcards containing terms like Refrigerant in the evaporator: a. Changes from a vapor to liquid b. Changes from a liquid to a vapor c. Stays in the vapor state d. Stays in the liquid state, What does a high evaporator superheat indicate?, A low evaporator superheat indicates: a. Undercharge b. System restriction c. Overcharge d. Dirt buildup e. Overcharge and ...Troubleshooting Subcooling Issues Common Causes of Low Subcooling. Low subcooling can be a bit of a headache. Some common causes include undercharged refrigerant, non-condensable gases, or a restricted expansion device. Identifying the culprit and resolving the issue will help get your AC back on track. High subcooling is usually accompanied by high head pressure because liquid is displacing available condensing area. Low superheat, low evaporator load - dirty filter, slipping belt, low fan speed, filthy coil. High superheat, evaporators being starved for refrigerant if suction pressure is low. If suction pressure is high and superheat seems ... Low airflow can be caused by a dirty or clogged air filter or a malfunctioning fan or blower motor, so be sure to investigate those components as the source of insufficient airflow. Low refrigerant charge. As seen in the table in Figure 2, a low refrigerant charge will result in a higher superheat and a lower subcooling and lower evaporator ...Oliver Wellington, HVAC Repair Expert. For a 410a refrigerant, the recommended superheat value is typically between 10°F and 12°F, while the ideal subcooling value ranges from 8°F to 12°F. However, these values can vary depending on the specific HVAC system and its requirements. The HVAC Alliance Expert team is available to help with any ...A network storage device is one of the best ways to keep your data backed up, but it can be a little pricey to set up and leaving a computer on all the time sucks a lot of power. I...Calculating superheat can tell us how far liquid Freon is traveling through an evaporator coil. If superheat is too high, there’s less liquid and more gas in the coil. This can cause overheating. If superheat is too low, more liquid and less gas are in the coil. This can cause flooding and damage in the compressor.This is important because, in cool mode, a dirty air filter caused low airflow on the evaporator. In those cases, you would typically notice a low suction pressure and a low superheat. In heat mode, a dirty air filter causes low airflow across the condenser. That can cause extremely high head pressure. In heat mode, a dirty outdoor coil can ...It's simply shedding heat energy, moving left all the way through the saturation dome, and even subcooling the refrigerant slightly at the end. Point 3: The "throttle" is the metering device that separates the high-pressure condenser from the low-pressure evaporator — usually a thin capillary tube in household refrigerators.Feb 5, 2017 ... ... it means to have high superheated, low superheat high subcooling and low subcooling. I explain the other things that affect the superheat and ...Actual line temp 50⁰F - SST 40⁰F = Superheat 10⁰F. As we will touch on later, superheat in the suction line is needed to ensure only vapor enters the compressor during a running cycle. ... When the compressor is powered, its job is to take low pressure, low-temperature refrigerant vapor from the suction line and compress it into a high ...non combustables in system...had to reclaim entire charge ,and recharge to make it work rightTXVs will generally stay at a 40-45 degree saturation temperature. If you're below 40 degrees, make sure your superheat and subcooling are on point. I had one yesterday that was running around 35 degrees, superheat was 30 degrees (25 degrees subcooling if anyone is wondering), which is too high for any TXV especially when it's 80 degrees inside.I kept arguing low air wouldn't cause low superheat and was providing confirming numbers by running tests with my house and shop systems. There may be some situations where a particular valve can't close down enough with a low heat load on a coil, resulting in low superheat. But generally speaking, whether the saturated temp is 25˚, 30˚, 40 ...High superheat= not enough refrigerant in the evaporator. Low subcool= not enough refrigerant in the condenser Compression ratio is fine, unlikely to be the valves. It isn’t possible for you to have liquid refrigerant in the liquid line if the line is hotter than the boiling point of the refrigerant. A Negative subcool number is not a thing.Low Water Flow-Verify design flow; Low Refrigerant charge: Verify Subcooling (15-20 F) and EXV 40-50% open at full load, 12 F superheat; Ratio= EXV % flow command / Superheat Control Compressor Flow estimate > 1.6; Incorrect Setting of Low refrigerant Temp Cutout (IOM). It should be set for type and percent (%) of glycol concentrationnon combustables in system...had to reclaim entire charge ,and recharge to make it work rightLow carb, high fiber foods can benefit almost everyone's diet. If you’re looking for some delish swaps, this list has lots of ideas. Even if you don’t follow a low carb diet, your ...WRONG, Low subcool means improper airflow over condenser. If you have improper air over condenser, you will have high head and actually a little higher Sub cooling. CORRECT, Low subcool = undercharge High subcool generally means overcharge. Thanks Mike Scott, don't let me discourage you. You are obviously thinking and trying to help others ...Low subcooling. High superheat. Figured it was low, put about 3 pounds in and subcooling never went up, super heat went down. Temp dif was better, but not great. I was thinking I had a restriction or bad txv, but I'm still learning and didn't really have a clue.Superheat is measured as the difference between the actual temperature of refrigerant vapor at a certain point and the saturation temperature of the refrigerant. It’s not complicated, but for a beginning tech, it might be.”. Superheat may be so complicated just because of the term “heat,” Tomczyk said. “Because something can be minus ...136K subscribers in the HVAC community. A subreddit for Heating, Ventilation, & Air Conditioning Technicians. If you are not a member of the trade…Aug 12, 2018 ... Comments49 · Saturation, Superheat, Subcooling · Charging an R-410A AC Unit that is Very Low on Refrigerant with the Subcooling Method! · AC U...An HVAC system is said to be running with high superheat or low subcool when there is a limited amount of refrigerant in both the evaporator coils and in the compressor. The possible reason for the high superheat and low subcool could be due. 1. Restriction in the liquid line. 2. Faulty metering system. 3. Excessive airflow through the ...no superheat, no subcooling. Here is the situation... Design pressures are 150/300psi with 12 degree subcooling... Actual conditions are 92Psi liquid at a temperature of 69F. High pressure side is at around 220Psi and about 12F BELOW saturation temperature. Cooling isn't really doing much indoors and runs constantly.Jun 26, 2021 ... Comments18 · Flooded Starts on HVACR Compressors · Copeland Discus - Full Inspection & Teardown · Why Measure Both Superheat and Subcoolin...A low suction superheat does not 'indicate' an overcharge. Low suction superheat is the result of too much refrigerant in the evaporator for the heating loading of the evaporator at that moment in time. Post the startup report data: Outdoor Ambient temperature. Condenser air temp in. Condenser air temp out.162. 25. I know that having both high superheat and low subcooling on an Air-Conditioner (A/C) is a strong indication that an air-conditioner does not have enough refrigerant. When the charge on an A/C is low, there is less refrigerant that enters the evaporator. When there is a lower amount of refrigerant entering the evaporator, it takes …Study with Quizlet and memorize flashcards containing terms like If the system suction pressure on a fixed metering device type unit is too high; the potential causes are;, TXV system problems can exhibit the five following symptoms:, Normal suction pressure & superheat, with low or high discharge pressure & subcooling on a TXV …Sep 19, 2014 · System Information R22 2.5 ton: Low Side: 115. High Side: 240. Return Air: 83. Suction Line Temp: 75. Measured Super heat: 5. Super heat should be around 15. Low superheat is an indication that liquid refrigerant not changing state in the evaporator and is possibly flooding back to the compressor. You get superheat when you have 100% vapor, and you have subcooling when you have 100% liquid; any liquid-vapor mixtures are in a saturated state. We usually measure superheat outside at the suction or vapor line. It's best to take the superheat reading as close to the port as possible. Anything in the saturated state is boiling; you can only ...First, measure the superheat right at the evaporator outlet in the same general location as the TXV bulb and equalizer. In most cases, the superheat at that point should be 5-10 degrees, but refer to the manufacturer's specs when in doubt. In some cases, you will not have a pressure port at the evaporator, so you must rely on a pressure reading ...To use our two examples from the previous paragraph, R134a at 0 psig and -5 F has 10 degrees of superheat, and the same refrigerant at the same pressure but at -20 F has 5 degrees of subcooling. These concepts of saturation, superheat, and subcooling are the foundation of all sealed system troubleshooting.CAUSE #2: Defective, plugged, or undersized metering device. Let's say a system has 45 psi suction pressure (converts to 22 ° F) and 68 ° F suction line temperature, the superheat is 46 ° F (68 minus 22). This indicates low refrigerant in the evaporator. However, before adding refrigerant, check the subcooling to be sure the problem isn't ...Aug 12, 2019 · On traditional HVAC/R systems, which utilize mechanical metering devices such as a TXV or cap tube, the superheat heating will vary between 8 °F to 20 °F. On newer systems, which use electronic expansion valves and solid state controllers, it is possible to see the superheat setting as low as 5 °F to 10 °F. A network storage device is one of the best ways to keep your data backed up, but it can be a little pricey to set up and leaving a computer on all the time sucks a lot of power. I...Join Date. Aug 2019. Posts. 106. Post Likes. “Normal” pressures, low subcool. A lot of times when I am checking TXV equipped units I’ll have normal pressures with a very low subcool. For example. 75 indoor. 20 delta t. 85 outdoor. Pressures around 320/130 psi.High subcooling is usually accompanied by high head pressure because liquid is displacing available condensing area. Low superheat, low evaporator load - dirty filter, slipping belt, low fan speed, filthy coil. High superheat, evaporators being starved for refrigerant if suction pressure is low. If suction pressure is high and superheat seems ...Low subcooling means that a condenser is almost empty. High subcooling means that a condenser is over field of liquid. 1) The amount of refrigerant entering the metering orifice is the Outdoor Dry bulb. 2) The total heat of the air entering the evaporator coil is the Indoor Wet bulb. With 95 degrees outside air.Normal Subcooling High Superheat. Find out what it means when your system has normal subcooling but high superheat, and learn how to diagnose and resolve this issue. Normal Subcooling Low Superheat. Learn about the implications of normal subcooling with low superheat and discover the potential causes and solutions for this unique situation.Many manufacturers recommend a subcooling range of 10° – 15°F, but always refer to manufacturer instructions to be sure. Just as there are two kinds of superheat, there are also two kinds of subcooling. They are condenser subcooling and total subcooling. We usually measure subcooling at the liquid line service valve.non combustables in system...had to reclaim entire charge ,and recharge to make it work right28. Post Likes. high super heat low suction. any ideas. I am working on a ruud heat pump. Freeze up problems. Low suction pressure, 24 superheat, 8 subcooling. 14 degree air drop across my coil. I have evacuated and wieghed in a charge r-22 and replaced txv. No kinks in line set and not a plugged filter dryer. .5 static pressure across my coil.For example, a very low reading (between 0 degrees to 10 degrees subcooling) indicates that the refrigerant did not lose the normal amount of heat in its …The high outdoor temps will probably always skew things a bit giving low superheat and low subcool. You're gonna have to learn to get the system in the best range possible for those really hot outdoor ambients! Reasonable head pressure, reasonable suction pressure and enough superheat to keep the compressor happy. It's gotta be tough!Low superheat in HVAC can be caused by factors such as low refrigerant charge, a faulty expansion valve, or insufficient heat load on the evaporator. What is normal superheat for 410a? Normal superheat for R-410A systems can range from 5-25°F (2-14°C) depending on the specific system and operating conditions.In an operating refrigeration circuit with a low side pressure of 120-psig and a low side line temperature of 50 degrees we have created 10 degrees of super-heat. This is important because super-heat is a measurement of metering. Without the ability to measure the metering of refrigerant in a circuit or the amount of heat being absorbed we ...A high superheat is an indication of either a low refrigerant charge or a liquid line restriction problem. To tell the difference between the two problems, we look at subcooling. A system with a low refrigerant charge will have a low subcooling. A system with a liquid line restriction will have a normal to high subcooling.Screw compressor discharge superheat. The screw compressor is a special type of compressor for particular applications. The discharge superheat is always lower in the screw compressor than the reciprocating compressor due to low discharge temperature. In a screw compressor, the oil is injected into the compressor; the oil cools the system.Are you planning a special event but worried about the cost of renting a banquet hall? Look no further. In this ultimate guide, we will provide you with all the information you nee...For superheat measurement, we use the blue low side gauge. The red one (high side) is for measuring subcooling on the liquid line. Needless to say, we: Don’t want a very low superheat (0°F, 1°, or 2°F) since this indicates liquid refrigerant might be entering the compressor. The compressor can only handle vapor, not liquid. If superheat is low and sub-cooling is low: Orifice could be too big, there is no orifice in the unit of the orifice is stuck and refrigerant is by-passing it. Superheat is telling you what is going on in the evaporator. High Superheat = Starved Evaporator Low Superheat = Flooded Evaporator Sub Cooling is telling you what is going on in the ... Both are out of cooling. and both have high superheat. like suction 20psi -7F, suction line temp 78F, head pressure 190psi, 97F, liquid line temp 72F, out door dry bulb temp 73F, Wet bulb at register indoor 19F, indoor dry bulb temp at register 78F. At the start of the suction.23. Post Likes. In low ambient conditions the reason the subcooling rises so much is because it starts to stack in the condenser. The reason for this is refrigerant is attracted to the coldest place in the system. During the winter the ambient conditions get below the temperature at the evaporator causing the refrigerant to naturally want to ...The system below is a walking freezer with a TEV. Refrigerant is R404a. Standard conditions are -10 °F box temperature for freezing (low temperature); 10 °F evaporator TD; 25 °F condenser split; 10 °F superheat; and 10 °F subcooling. From the information given on the diagram, answer the question below.LOW SIDE SYSTEM TEMPERATURES AND PRESSURES Refrigerant State T, ºF R-410A, psig Superheat/Subcool Low Pressure Saturated 45 131.1 Low Pressure Superheated Vapor 53 131.1 Superheat = T - T sat = 53º - 45º = 8ºF High Pressure Gas 180 448.2 High Pressure Saturated 125 448.2 High Pressure Liquid 110 448.2 Subcool = T satTroubleshooting low superheat. Low superheat values could result from an overcharged system, a dirty condenser coil, or a malfunctioning metering device. Think of it like diagnosing a car that's not running smoothly - you need to investigate and address the issue! Troubleshooting high subcoolingThis article explains how subcooling affects the efficiency of your air conditioning system. Read on to learn more about the subcooling process. Financing. 615-746-6390. Emergency Service. ... Perhaps the most common cause of insufficient subcooling is an abnormally low refrigerant charge. Lack of refrigerant usually means that your system ...Dynaboard built a low-code web application development tool to bring together product managers, designers and developers in a single tool. Dynaboard founder Alex Kern has been prog...Common Causes of High or Low Superheat. Superheat is a crucial factor in refrigeration systems that controls the temperature and pressure of refrigerants. It measures the amount of heat added to vapor from its boiling point at a particular pressure, indicating how well the evaporator coil transfers heat between refrigerant and air.Normal Subcooling High Superheat. Find out what it means when your system has normal subcooling but high superheat, and learn how to diagnose and resolve this issue. Normal Subcooling Low Superheat. Learn about the implications of normal subcooling with low superheat and discover the potential causes and solutions for this unique situation.Subcooling is a measurement of how much the liquid in the condenser cools down before exiting. When the hot gas in the condenser first turns to liquid, its temperature is at the saturation point. This means that the temperature of the liquid as it first forms is at the same temperature at which the refrigerant is condensing — the saturation ...subcooling somewhere around 12-15 degrees F. Suction Pressure around 21-22 psia = -15 to -14 deg.f. Suction line temp. leaving evap. = -12 to -2 deg. F. (The temperature swing is -12 to -2) It stays quite stable. Isn't radical with the temp. swing. box temp. -5. It's an empty walk in box about 7 x 10 foot square.Great discussions are par for the course here on Lifehacker. Each day, we highlight a discussion that is particularly helpful or insightful, along with other great discussions and ...28. Post Likes. high super heat low suction. any ideas. I am working on a ruud heat pump. Freeze up problems. Low suction pressure, 24 superheat, 8 subcooling. 14 degree air drop across my coil. I have evacuated and wieghed in a charge r-22 and replaced txv. No kinks in line set and not a plugged filter dryer. .5 static pressure across my coil. High superheat, low subcooling—or high subcooling, low superheat—can tell us a story about the system and its needs. Ensuring that a system is fully operational within the appropriate ranges means that you need the right tools to read subcooling and superheat temperatures. Evap would show a higher suction pressure but low superheat due to flooded condition. shophound Okay, but not releevant to my statements. udarrell The reversing valve can be ruled out easily because if it was leaking discharge gas to suction, there would be a greater heat rejection load imposed on the outdoor coil, reducing …If the metering device is a fixed orifice such as a piston or capillary tube, the refrigerant charge of the system can be checked with Total Superheat. If the metering device is a TXV then the refrigerant charge can be checked with Subcooling. See the Picture below. If the unit has a TXV, check for the Target Subcooling posted at the outdoor unit.The system below is a walking freezer with a TEV. Refrigerant is R404a. Standard conditions are -10 °F box temperature for freezing (low temperature); 10 °F evaporator TD; 25 °F condenser split; 10 °F superheat; and 10 °F subcooling. From the information given on the diagram, answer the question below.One of the most common reasons for low superheat is due to reduced airflow. With reduced airflow, there isn't enough warm air to vaporize the refrigerant. What does low Subcool mean? Low Subcooling is an indication that not enough refrigerant is contained or "packed" in the condenser. This can be due to undercharge, poor compression, or a ...R134a Low Subcooling, High Superheat. This is regarding the refrigeration system for a water cooler. The evaporator is immersed in the water to be cooled. The following information is available at 25 mins after starting the compressor: When water temperature was 7.8 deg. C. Evaporator Inlet: 0.7 deg. C. Suction: 23 deg. C. Discharge: 72.6 deg. C.High compressor superheat; Low condenser subcooling; Low compressor amps; Low evaporator temperatures and pressures; and; Low condensing temperatures and pressures. Again, the symptoms of a liquid line restriction are very similar to a system with a refrigerant undercharge; however, the undercharged system will have low …That’s because low charge results in high superheat AND low subcooling (we have covered this in high superheat low subcooling issues here). We are left with only 2-3 culprits that can actually cause both high superheat and normal subcooling. These are: Too high indoor CFMs. Too high indoor load. Faulty measurement. Let’s look at all these …Single-component refrigerants boil at one temperature, and superheat or subcool measurements are compared to that boiling point. Blends change temperature while boiling or condensing, so the end points of the glide must be known in order to calculate superheat or subcool temperature. Troubleshooting Single component Blends Superheat vapor ...

A low condenser subcooling can mean a low charge. A high condenser subcooling can mean an overcharge, but not always. Capillary tube systems: This is not true for capillary tube systems because the majority of them have no receiver. A capillary tube system can run high subcooling simply from a restriction in the capillary tube or liquid line.. How many seats are on a southwest 737

low subcool low superheat

For example, a very low reading (between 0 degrees to 10 degrees subcooling) indicates that the refrigerant did not lose the normal amount of heat in its …Low subcooling. High superheat. Figured it was low, put about 3 pounds in and subcooling never went up, super heat went down. Temp dif was better, but not great. I was thinking I had a restriction or bad txv, but I'm still learning and didn't really have a clue.This is an intermediate discussion on superheat and subcooling in which I go over why superheat and subcool are important. About Lianna; Posts; Contact Me; Home; Superheat and Subcooling Part II. I wrote about the basics of superheat and subcool, which you can read here. ... Low superheat (aka a "flooded evaporator") can be caused by many ...Low Superheat Low Subcooling: Learn To Fix It. Low superheat and low subcooling are the indicators for your evaporator to be low on heat and have a limited refrigerator in its condenser. We will …The amount of superheat we have is also important. A superheat that is too low risks going to zero and causing compressor damage by flooding the compressor. A superheat that is too high means that the evaporator coil is being underfed with refrigerant, which will lead to low capacity, low efficiency, and compressor overheating on most systems.That means understanding and measuring all three types of superheat: evaporator, total, and duct system. 1. Evaporator superheat. To measure evaporator (indoor coil) superheat, first measure the suction line temperature at the evaporator outlet. Next, measure the refrigerant pressure at the suction line of the indoor coil. High pressures can cause refrigerant leaks at the condenser, leading to high superheat and low subcooling. To avoid these issues, ensure sufficient airflow by keeping condenser coils and fins clean. 2. Malfunctioned Metering Devices. The metering tool controls the refrigerant flow. A malfunctioning tool can result in refrigerant flow ... Low superheat high subcooling is a common issue with AC units. There are 5-6 low superheat causes and 3 high subcooling causes. By comparing these causes, we can see which ones are the reason we have low superheat and high subcooling. Here is a chart of low superheat causes (on the left) and high subcooling causes (on the right). The culprits ...Determine 407c superheat vapor temperature difference and subcooling liquid temperature difference. On the 407c PT chart, ... The equalized system will have the same R407c pressure on the low and high sides. If the system is not equalized, the saturated state is only found at the evaporator (measured outdoor vapor service port) and condenser. ...Added about 15 ounces of refrigerant but no change to subcooling. Contractor's Assistant: Anything else we should know to help you best? It's an R-410a system. Outdoor temp was 80 degrees at condenser; liquid line measured temp. was 86 degrees; high side pressure was 267 psi; low side pressure was 125 psi.Like superheat, it describes the volume of vapor and liquid refrigerant inside of our condenser coil, except for subcooling we are measuring the liquid as opposed to the vapor. A low subcooling means most of our condenser is filled with vapor, and a high subcooling means most of our condenser is filled with liquid.Jess Gordon is the service manager at Tempo Mechanical Services, Irving, TX. The company was Contracting Business magazine's 2003 Residential Contractor of the Year. Jess can be reached at 972-579-2000, or by e-mail at [email protected]. Superheat is a way to ensure that the system is boiling off all of the liquid before it exits the evaporator.Superheat: 51 F Subcool: 8 F Trane R410A system has a design subcool of 10 +/- 3 degrees so my subcooling is within the threshold. I did not see a filter drier on either the suction or discharge lines to take a temperature drop across to see if there is more than a 2 degree difference aka change that out.Sep 3, 2020 ... In this video you can clearly see from start to finish a refrigeration system being charged using superheat and subcooling method..